Wire Size Calculator

Enter the load — get the AWG. Add a distance to auto-check voltage drop and upsize if needed.

How the size is chosen

The calculator walks the NEC 310.16 ampacity column for your material and termination rating and returns the smallest conductor whose ampacity meets the load. For 14, 12 and 10 AWG it automatically applies the NEC 240.4(D) small-conductor caps (15/20/30 A on copper) — the rule that trips up most quick chart lookups. If you enter a distance, it also checks the run against the 3% voltage-drop guideline and recommends the next size up when the run is too long.

Typical picks (copper, 75°C)

LoadCopperCommon use
15 A14 AWGlighting circuits
20 A12 AWGreceptacles, small appliance
30 A10 AWGdryer, water heater
40 A8 AWGrange
50 A8 AWGEV charger (non-continuous rating)
60 A6 AWGsubpanel feeder
100 A3 AWGsubpanel / small service
Continuous loads (EV charging, heating) must be sized at 125% of the load per NEC 210.19 — enter the adjusted amps. Derating for ambient heat or bundled conductors is not included in v1.

Related: full ampacity chart · voltage drop calculator · conduit fill calculator