Electrical calculators that answer on the first screen
Wire size, conduit fill and voltage drop — instant results, no signup, phone-first.
What these tools do
Every branch circuit raises the same three code questions: what gauge wire can carry the load (NEC 310.16 ampacity, with the 240.4(D) small-conductor limits applied automatically), how many wires legally fit in a conduit (NEC Chapter 9, 40% fill), and whether the run is too long for acceptable voltage drop (3% guideline). TradeCalcs answers all three from one screen, using the same tables an inspector will check against.
Common quick answers
50 amps at a 75°C termination calls for 8 AWG copper; on a 240 V, 75 ft run that lands at ≈2.4% voltage drop — inside the guideline, while a 100 ft run pushes past 3% and gets upsized to 6 AWG. 3/4″ EMT holds up to 16 × 12 AWG THHN at 40% fill. A 20 A load on 12 AWG copper at 120 V exceeds the 3% guideline past roughly 50 ft one-way — the distance check upsizes the conductor for you.